ETITEC CM T23 275/20 1+1 RC Protecție supratensiuni
- Cod ETI:
- 002440655
- Funcție:
- SPD
- Tip:
- T2, T3
- Tensiune maximă de funcționare continuă în AC Uc:
- 275 V
- In (8/20) :
- 20 kA
- Tip curent:
- AC
- Tensiune nominală AC:
- 230 V
- Parte superioara - Nivel de protectie a tensiunii:
- 1,5 kV
- Semnalare la distanță :
- Yes
- Curent de scurgere :
- Yes
- Sistem rețea:
- TT/TN-S
- Numarul de module :
- 2
- Instalare:
- Home and residental building protection
- Adancime incorporata:
- 70 mm
- Grad de protecție IP:
- IP20
- Tehnologie aplicata :
- MOV
- Grup Catalog:
- ETITEC CM
6 Documente
21 Logistică
Produs
- Greutate
- 0,691 kg
- Net width
- 17,7 mm
- Net height
- 105,4 mm
- Net depth
- 77,13 mm
- Stock unit of measure
- pcs
Ambalare de bază
- Basic packaging quantity
- 1 pcs
- EAN code for a basic packaging
- 3838895918455
- Basic packaging weight
- 0,164 kg
- Basic Packaging Dimensions Height
- 83 mm
- Basic Packaging Dimensions Width
- 26 mm
- Basic Packaging Dimensions Depth
- 118 mm
- Basic packaging volume
- 0,255 dm³
Ambalare transport
- Transport packaging quantity
- 15 pcs
- EAN code for a transport packaging
- 3838895918462
- Transport packaging weight
- 2,534 kg
- Transport Packaging Dimensions Height
- 90 mm
- Transport Packaging Dimensions Width
- 355 mm
- Transport Packaging Dimensions Depth
- 118 mm
- Transport packaging volume
- 3,77 dm³
- Pallet quantity
- 3.975 pcs
- Customs tariff
- 85363090
19 ETIM
- Max. conductor cross section flexible (fine-strand)
- 6 mm²
- Max. discharge surge current (8/20)
- 40 kA
- Number of conductors (without earthing)
- 2
- Voltage protection level L-N
- 1,5 kV
- Nominal voltage AC
- 230 V
- Max. conductor cross section solid (solid, stranded)
- 10 mm²
- Degree of protection (IP)
- IP20
- Mounting method
- DIN rail (top hat rail) 35 mm
- Construction size
- 1 modular spacing
- Short-circuit breaking capacity (Isccr)
- 25 kA
- System configuration TN-S
- Da
- Voltage protection level
- 1,5 kV
- System configuration TT
- Da
- Signalling at the device
- Optical
- Category type 2
- Da
- Voltage protection level N-PE
- 1,5 kV
- Max. continuous voltage AC
- 275 V
- With remote signalling contact
- Da
- Nominal discharge surge current (8/20)
- 20 kA