KZS-AFDD 3M2p A C15/0.03 Dispozitiv detectare arc (AFDD
- Cod ETI:
- 002173879
- Tensiune nominală AC:
- 230 V
- Curentul rezidual de operare :
- 0,03 A
- Aplicație:
- IEC/EN 61009
- Curent nominal:
- 15 A
- Tip:
- A
- Curent de defect nominal:
- 0,03 A
- Caracteristică de întrerupere:
- C
- Număr de poli:
- 2
- Capacitatea de rupere:
- 10 kA
- Secțiune transversală nominală:
- 1-25 mm²
- Standarde:
- IEC/EN 61009
6 Documente
21 Logistică
Produs
- Net depth
- 73,31 mm
- Greutate
- 377 g
- Net width
- 53,7 mm
- Net height
- 88,7 mm
- Stock unit of measure
- pcs
Ambalare de bază
- EAN code for a basic packaging
- 3838895869399
- Basic packaging weight
- 0,377 kg
- Basic Packaging Dimensions Depth
- 0,056 m
- Basic Packaging Dimensions Height
- 0,08 m
- Basic packaging volume
- 0 m³
- Basic Packaging Dimensions Width
- 0,095 m
- Basic packaging quantity
- 1 pcs
Ambalare transport
- Transport packaging weight
- 12,791 kg
- Transport packaging volume
- 0,017 m³
- Transport packaging quantity
- 33 pcs
- Customs tariff
- 85362010
- Transport Packaging Dimensions Height
- 0,25 m
- Transport Packaging Dimensions Width
- 0,235 m
- Transport Packaging Dimensions Depth
- 0,295 m
- EAN code for a transport packaging
- 3838895869412
- Pallet quantity
- 1.716 pcs
29 ETIM
- Rated insulation voltage Ui
- 400 V
- Built-in depth
- 69 mm
- Leakage current type
- A
- Connectable conductor cross section solid-core(Max)
- 25 mm²
- Surge current capacity
- 0,25 kA
- Voltage type
- AC
- Connectable conductor cross section multi-wired(Max)
- 25 mm²
- Rated impulse withstand voltage Uimp
- 4 kV
- Degree of protection (IP)
- IP20
- Ambient temperature during operating(Min)
- -25 °C
- Release characteristic
- C
- Over voltage category
- 3
- Rated fault current
- 0,03 A
- Number of poles (total)
- 2
- Disconnection characteristic
- Undelayed
- Connectable conductor cross section solid-core(Min)
- 1 mm²
- Pollution degree
- 2
- Frequency
- 50 Hz
- Connectable conductor cross section multi-wired(Min)
- 1 mm²
- Rated short-circuit breaking capacity according to EN 61009
- 10 kA
- Concurrently switching neutral conductor
- Da
- Number of protected poles
- 2
- Rated voltage
- 230 V
- Current limiting class
- 3
- Rated short-circuit breaking capacity according to IEC 60947-2
- 10 kA
- Rated current
- 15 A
- Ambient temperature during operating(Max)
- 40 °C
- Rated short-circuit breaking capacity Icn according to EN 61009-1
- 10 kA
- Width in number of modular spacings
- 3